The AR5 kit includes a palm-top energy & harmonics analyzer along with three clamp-on CTs and four voltage probes. The kit is portable, light weight, easy to operate, and ideal for regular checkups. It can be used for single or three phase, balanced or unbalanced systems, HT or LT system.
Simultaneous viewing of all parameters on a single screen
Suitable for HT & LT
Displays max & min values
Built-in rechargeable battery with 8-hr backup
Real-time clock
User programmable sampling period and time
Displays bar graphs and wave forms on LCD screen
Measures harmonics up to 50th level for Voltage & Current and THD in %
1MB RAM storage capacity (stores 30 parameters for 15 min interval for 80 days)
Powerful AR5 Power Vision Software for downloading and analyzing from meter to PC
AR5-L Series This evolved version of AR5 includes additional features like:
Comprehensive status of battery usage
Discharge level
Charging level
Hours of battery use
Auto detection of connected CT ratio
CT measuring range from 1% of CT primary
Backlit LCD display
Four current probes for 3 phases & 1 neutral
Password protection
Technical Specifications
Power Supply & Measurement
CTs
Sensing : 1 Phase/3Phase (3 Wire/4Wire)
Measuring Range : 1% CT Primary
Working Frequency : 40 - 1000 Hz
2000/200 : 333X 133X 52mm
Cable Dia : 70 mm
Busbar Dia : 120 X 20
Weight : 1.8 Kgs
1000A & 500A : 210 X 100 X 38 mm
Cable Dia : 45 mm
Busbar Dia : 45 X 10 mm
Weight : 0.51 Kg
100A : 95 X 42 X 22 mm
Cable Dia : 15 mm
Busbar Dia : 17 X 15 mm
Weight : 0.15 Kg
5A : 115 X 32 X 12 mm
Cable Dia : 15 mm
Weight : 0.15 Kg
Measurement : True RMS
Voltage Input : 110 (selectable at site)
Current Input : Through Current Probes 2000+200A, 1000A or 5A
Auxiliary Input :240 V ac(Battery Charging)
Accuracy Current - 0.5% of reading +2 digit
Voltage - 0.5% of reading +2 digit Power - 1.0% of reading +2 digit
Power Factor 0.5 lag - Unity - 0.5 lead
Frequency variation 45 to 60 Hz
Overload capacity a) Voltage up to 500V (p-n) and 850V (p-p) b) Current up to 150% In
Operating temperature : 0 to 50 c ambient
Humidity : < 90% RH Non Condensing Display : 160X160mm Pixels L.C.D. Dimensions : 200 x 130 x 62 mm (Meter) Weight : 800 gms (Meter) 13 Kg (Kit 5)
Standards: Confirms to IEC 1010-1, EN 61010-1, IEC 521, IEC 564
Ordering Information
Model
Kit 5
Kit 4
Kit 3
AR5
Suitable for both HT & LT measurements with Current up to 2000+200A
Smart Analyser
Built-in Energy
Program
3 nos. CTs
2000+200A
3 nos. CTs 5A
Power Supply cum
RS 232 port
Harmonics cartridge
Disturbance cartridge
Power Vision
Software
Carrying Case
Suitable for LT Bus Bar with Current upto 2000+200A
Smart Analyser
Built-in Energy
Program
Built-in Harmonics
cartridge
3 nos. CTs
2000+200A
4 nos. Voltage
Probes
Power Supply cum
RS 232 port
Power Vision
Software
Carrying Case
Suitable for LT Bus Bar with Current upto 1000A
Smart Analyser
Built-in Energy
Program
Built-in Harmonics
cartridge
3 nos. CTs 1000A
4 nos. Voltage
Probes
Power Supply cum
RS 232 port
Power Vision
Software
Carrying Case
AR5-L
All the Accessories of AR5-Kit 5 Plus:
1000A CTs 1 No. for
Neutral Current
Measurement
All the Accessories of AR5-Kit 4 Plus:
1000A CTs 1 No. for
Neutral Current
Measurement
All the Accessories of AR5-Kit 3 Plus:
500A CTs 1 No. for
Neutral Current
Measurement
Portable Power Analyzers-C80
Features
True RMS measurements
Auto detect of ammeter clamp of CT ratio
Displays RMS, maximum and minimum
Low battery indicator
Measures V, A, Hz, kW, kVA, PF, kWh, kVARh, %THD
Displays measured and recorded parameters
Measures leakage currents
Calculates the capacitor bank required by an installation (load)
Calculates the reactive energy that a capacitor bank will correct
Stores all parameters every 15 minutes for one day
In-built back up battery for recording of parameter (200hrs)
Displays phase sequence
Displays required kVAr for improving the PF to desired level
Alarm setting
Applications
Motor control center, Genset panels, Individual load centers
All type of installations: motors, pumps, lifts, industrial, domestic, etc.