Features
-
True RMS
- Suitable for HT & LT
- Frequency & RPM measurement
- Records run hours, off hours, and interruptions
- Generation of High-Low profiles for all power parameters with date and time
- Accuracy Class 1.0, 0.5 and 0.2
- Auto scaling from kilo to mega
- Auto scrolling
- Auto reset option
- Up to 10 years' backup of data and settings
- Built-in RTC and RS 485 port
- Portable kit option with clamp-on CTs & voltage probes
- Maximized resolution through floating decimal point
- Sharp, high visibility display
- Import/Export option
- Compact size Bezel 192 x 144mm. Depth
behind bezel 110mm
- Quick & easy installation
- TOU option
The EM 3000 series meters are used to measure:
- Voltage: Phase to Phase and average
- Voltage: Phase to Neutral and average
- Voltage: Neutral to Earth
- Voltage: Phase angle
- Current: Phase-wise, Average and Neutral Current
- Current: Phase angle
- % Total Harmonic Distortion of voltage & current wave forms phase-wise
The EM 3000 series has three different models for different applications:
Power & Energy Monitor EM 3360
- Voltage: Phase to Phase and average, Phase to Neutral and average, Neutral to Earth
- Phase angle: Voltage and Current phase wise
- Current: Phase-wise, Average and Neutral Current
- % Total Harmonic Distortion of voltage & current wave forms phase-wise
- Monitoring of all power & energy parameters - total as well as phase wise
- 4 high and 4 low profiles for instantaneous parameters with day, date and time
- Optional TOU for 8 intervals and 7 seasons for energy parameters
Tri-vector Monitor EM 3480
All features of EM 3360 meter plus
- EB Meter cross-check
- Monitors demand parameters: Instantaneous & maximum demand, with day, date & time
- Synchronizes automatically with EB meter
- Records High-Low profile of maximum demand
- Generates Demand Profile at 19 Demand Levels for setting realistic demand targets according to user-programmed Demand Level 0 and step size
- Optional TOU for 8 intervals & 7 seasons for energy and demand parameters
Smart Demand Controller EM 3460 All features of EM 3480 meter plus
- User programmable upper limit and lower limit of kW or kVA parameters, essential load and prediction interval for sophisticated demand control
- Demand intervals selectable from 1 to 30 minutes
- Demand control through unique predictive technique and sliding window integration which leads to: Reduced energy losses, improved load factor & minimal disruption in operations
- 3 changes over potential-free control outputs for: Predicted demand exceeds target, demand exceeds target & restore load
- Spare load and predicted demand parameters gives advance warning for planned demand control
| Technical Specification |
Sensing |
3 Phase, 3 Wire / 4 Wire (field configurable) |
Measurement |
True RMS |
Voltage Input |
110 to 415 V nominal ( Range 80 - 500 V) |
Current Input |
5 or 1 Amp (Factory set ) nominal |
Maximum Current |
150 % of nominal |
Burden on PT or CT |
0.2 VA Max |
Accuracy ( For V, A, PF, & all Power & Energy Parameters ) |
Class 1.0 |
+ (0.2 % of Full Scale + 0.8 % of reading + 1 digit ). |
Class 0.5 |
+ (0.1 % of Full Scale + 0.4 % of reading + 1 digit ). |
Class 0.2 |
+ (0.05% of Full Scale + 0.15% of reading + 1 digit ). |
Accuracy of Hz |
0.2 % of reading |
Accuracy of ø |
10 ° ( 20 % to 150 % of Full Scale ) |
Display update |
Every 1 second ( Demand Par - 15 Secs ) |
Keyboard |
Easy to operate sealed Membrane type |
Auxiliary Supply |
Factory Set, Single 50 Hz 240V ( 190 - 270 V ) or
110V ( 85 - 130V ). Burden 5VA max.
|
Frequency |
50 Hz + 5%, 60 Hz |
Power Factor |
0.5 PF Lag - Unity - 0.8 PF Lead |
Dimensions |
Bezel 192 x 144mm.
Depth behind Bezel 110mm
|
Weight |
1800 gms. Approximately |
Panel Cut out |
186 x 138mm ( + 1 - 0 mm) |
Operating temperature |
0 - 60 ° C ambient |
|