These basic meters used for current, voltage, and frequency measurement come with field configurable full-scale settings and a built in selector switch for 3-phase measurements.
For Frequency Meter only : 4 Digits Display
a) Standard Model : Read Aux. Supply Frequency
b) With External Sign option : 20.00 - 99.99 Hz
(40 V- 500 V)
Technical Specifications
a.
Aux. Supply
Nominal 110V Range 80 - 150V
Nominal 240V Range 170 - 300V
b.
Accuracy
For Hz meters
Class 1.0 [ + (1% of Full Scale+1 Count)]
Class 0.5 [ + (0.5% of Full Scale+1 Count)]
Class 0.2 [ + (0.2% of Full Scale+1 Count)]
c.
Resolution
1 count in 100 counts or better
d.
Display
3 digits for nominal full scale counts upto 800
3 ½ digits for nominal full scale counts from 800 to
1600 for Class 0.5 only.
e.
Burden
0.2 VA max. per phase (Volts/Amps Input)
3 VA max. on Auxiliary supply
f.
Ambient
Temperature 0 - 50 o C
Humidity < 95% Non condensing
g.
Weight
320 - 400 gms depending on Model
h.
Dimensions
Bezel : 96 X 96 mm
i.
Depth
80 mm behind bezel
j.
Panel Cut-out
k.
Mounting
Panel Mounting
l.
Warranty
1 year from date of invoice
Ordering Information
SI.
Parameters
1 Phase
3 Ph 3 Wire
3 Ph 4 Wire
1
2
3
4
5
6
7
8
Wiring
Voltage Input
Current Input
PT Ratio
CT Ratio
Auxiliary Supply
Accuracy Class***
Mounting Option
1Phase
240V**
5A or 1A
33kV / 110V*
1200 / 5A*
240V / 110V
0.5 or 1.0
Flush Type
3 Ph 3 Wire
110V or 415V
5A or 1A
33kV / 110V*
1200 / 5A*
240V / 110V
0.5 or 1.0
Flush Type
3 Ph 4 Wire
110V or 415V
5A or 1A
33kV / 110V*
1200 / 5A*
240V /110V
1.0
Flush Type
* One typical value shown above, meters can be supplied with others ratios also.
**63.5V,110V & 415V also available.
*** Refer Models.
Note:
Input Voltage for:-
3290 : 10 to 500 Volts DC nominal.
3291 : 75/60 m Volts, DC shunt.
To enable prompt processing of your orders, please include the above details in your orders.