MeasureDetectControl

Smart Power Analyzers - CVM series*

The CVM Series multi-function meters are programmable power analyzers with multi parameter display and various plug-in modules for relay outputs, individual harmonics, 4-20 mA output and in-built memory

  Downloads
  Product Catalog
  Product Datasheets (PDF)
  (PDF, 1.86 MB)
  Warranty Certificate
  Warranty Certificate (PDF)
  (PDF, 178 KB)
FAQ
  CVM 96
  CVM 144

Features

  • True RMS
  • Measures 30 parameters
  • 3 phase 4 wire and 3 phase 3 wire
  • MAX and MIN values stored in internal memory, instant display
  • Automatic scaling
  • Three-line, bright LED display
  • Demand with Automatic sliding window technique
  • Four key tactile-keyboard for control and setting actions
  • Isolated current signal input
  • 2 relay output: programmable for controlling instantaneous parameter, demand parameter or energy pulse
  • Displays screen off mode Programmable
  • Two Quadrant measurement
  • Measures Individual Current Harmonics up to 15th and THD of V&A

CVM96

  • Suitable for both HT/LT applications
  • RS-485 communication
  • Programmable Power Demand time period (from 1 to 60 min.)
  • Programmable Power Demand parameter (kW, kVA or 3 phase currrent)
  • 96 * 96 mm size
Technical Specification
Power Supply Auxiliary Supply 240 V AC, 50 to 60 Hz (110 V AC/DC on request)
Voltage Tolerance + 10% / -15%
Consumption 3 to 5 VA according to the type
Relay Output 2 NO Contact
Contact rating 2500 VA
Operating Temperature 0 to + 50 ° C
Measuring Circuit Measuring Voltage (L-N/ L-L)

20 - 300 V (L-N)
20 - 520 V (L-L)

Rated Current (Insulated inputs for the ITF type) -/5 A (1A on request)
Permanent Overload 120% (6 A)
Current Circuit Burden 0.6 VA
Accuracy Class Voltage 0.5% of reading ± 2 Digits
Current 0.5% of reading ± 2 Digits
Power 1% of reading ± 2 Digits


Accuracy Test Conditions

. Voltage & Current Transformers errors not included
. Power Factor between 0.5 and 1
. Measurement range 5 to 100% full scale



Construction Characteristics

Mounting

Flush Mounting, Bezel - 96 X 96 mm

Connection

Terminal Connection

Protection

IP 54

Panel Cutout

92 X 92 mm Depth : 84 mm

Weight

520 Grams



Parameter Display & Communication

Parameters

Symbol

L1

L2

L3

Average

Voltage (phase-neutral)

V  

 

Voltage (phase-phase)

V  

 

Current

A

Frequency

Hz

 

 

 

Active power

kW

Reactive power L

kvarL

Reactive power C

kvarC

Apparent power

 

 

 

 

Power factor

PF

Cos j

 

 

 

 

Power demand

Pd

 

 

 

kW h

energy

 

 

 

kvarhL

energy

 

 

 

kvarhC

energy

 

 

 

Neutral current

IN

 

 

 

Voltage THD

% THD-V

 

Current THD

% THD-A

 

Individual harmonic current content (Up to the 15th)

 

 

Available: : Display and communications : Communication

CVM144

  • Compact and panel mounting device
  • Optional (one/two) 4-20 mA (programmable to any instantaneous parameter)
  • Optional: Modbus & Profibus compatible, 3 Analog inputs and 2 outputs, 3 Digital inputs and 2 outputs. RS 485 or RS 232
Technical Specification
Power Supply Auxiliary Supply 240 V AC, 50 to 60 Hz (110 V AC/DC on request)
Voltage Tolerance + 10% / -15%
Consumption 3 to 5 VA according to the type
Relay Output 2 NO Contact
Contact rating 2500 VA
Operating Temperature 0 to + 50 ° C
Measuring Circuit Measuring Voltage (L-N/ L-L)

20 - 300 V (L-N)
20 - 520 V (L-L)

Rated Current (Insulated inputs for the ITF type) -/5 A (1A on request)
Permanent Overload 120% (6 A)
Current Circuit Burden 0.6 VA
Accuracy Class Voltage 0.5% of reading ± 2 Digits
Current 0.5% of reading ± 2 Digits
Power 1% of reading ± 2 Digits

Accuracy Test Conditions

. Voltage & Current Transformers errors not included
. Power Factor between 0.5 and 1
. Measurement range 5 to 100% full scale


Construction Characteristics

Mounting
Connection
Protection
Panel Cutout
Weight

Flush Mounting, Bezel - 144 X 144 mm
Terminal Connection
IP 54
138 X 138 mm Depth : 76 mm
700 Grams



Technical Specification - Parameter Display & Communication

Parameters

Symbol

L1

L2

L3

Average

Voltage (phase-neutral)

V  

 

Voltage (phase-phase)

V  

 

Current

A

Frequency

Hz

 

 

 

Active power

kW

Reactive power L

kvarL

Reactive power C

kvarC

Apparent power

 

 

 

 

Power factor

PF

Cos j

 

 

 

 

Power demand

Pd

 

 

 

kW h

energy

 

 

 

kvarhL

energy

 

 

 

kvarhC

energy

 

 

 

Neutral current

IN

 

 

 

Voltage THD

% THD-V

 

 

CVM Series DIN Rail Mounted

  • True RMS measurement of HT, LT circuit
  • DIN rail mounting device
  • Measures over 30 parameters
  • MAX and MIN values stored in internal memory, instant display
  • Automatic scaling display
  • Demand with Automatic sliding window technique
  • Harmonic Distortion measurement (THD of V&A: Individual phase)
  • PT primary and secondary, CT primary programmable
  • RS 485 or RS 232 communication

There are 3 models in CVM Series, DIN rail mounted model

CVM BC: Power and Energy Analyser
  • Measurement of Phase - Neutral or Phase -Phase voltage
  • 2 relays for alarm settings
  • Parameter display with 2 rows of LCD
CVM BD: Power and Energy Analyser
  • All features of CVM BC plus
  • Four quadrant measurements
  • Memorizes max and min values
  • Parameter display with 3 line numerical LCD
  • Possible to expand 4 to 8 nos of 4-20mA output
  • Models available CVM-BD-RED-H, CVM-BD-RED-C2-H
CVM BDM: Power and Energy Analyser
  • All features of CVM BD plus
  • Built in internal memory of 1MB
  • 2 luminous LED s to indicate CPU operation and communications
  • Backlit display
  • Measurement of voltage and current harmonics upto 15th
  • Flicker measurement
  • Calculation of Neutral current
  • Power demand and alarm setting option
  • Password protected
  • Modbus RTU communication protocol RS485 or RS232
  • Power vision software for analysis of measured parameters

* Available only in India

VAF meters - DM32 series
Electronic kWh meters-DM52 series
DM52 series Tariff version
ELF series
EM 6400 DigitAN™ series
EM 6438 Dual Source Energy Meter
EM 3000 series
Portable power analyzers
Power Analyzers - CVM series
Synchronisation Relay-SynchroMax
Certifications